Alison Hazel

Alison Hazel

11/08/2017

LCR Meters

Amprobe LCR55A Capacitance Tester


The ultimate electronic component verifier measures inductance, capacitance, resistance, transistors, diodes and microwave diodes.

  • The ultimate component checker measures inductance, capacitance, resistance, transistors, diodes and microwave diodes
  • Plug-in test slots and test leads with threaded alligator clips
  • Oversized, digital display
  • Data Hold and Max Hold
  • "Zero Adjust" Pot for Ohms
  • Low Battery Indication
  • Auto-Power Off

REED R5001


  • Measure inductance/capacitance/resistance with secondary parameters including dissipation
factor (D), quality factor (Q), phase angle (Ø), equivalent series/parallel resistance (ESR or Rp)
  • Auto ranging operation for AC impedance and DE resistance measurement
  • Auto LCR smart check and measurement
  • Series/Parallel modes
  • Ls/Lp/Cp with D/Q/Ø/ESR parameters
  • Support DCR mode 200 to 200MΩ
  • High accuracy with 4 or 5 terminal Kelvin measurement
  • Testing frequency is up to 10kHz and output frequency is up to 100kHz
  • Dual display with backlight
  • Data hold function
  • Low battery indication with auto power off
  • Dust and water proof to IP67

11/08/2017

Clamp Meters

Fluke 376 Clamp Meter


The Fluke 376 Clamp Meter offers improved performance perfect for a wide range of current measurement situations. With true-rms voltage and current measurements, the Fluke 376 can read up to 1000 V and 1000 A in both ac and dc modes.

Features and benefits

  • CAT IV 600 V, CAT III 1000 V
  • True-rms ac voltage and current for accurate measurements on non-linear signals
  • Min, max, average and inrush recording to capture variations automatically
  • Integrated low pass filter and state of the art signal processing allows for use in noisy electrical environments while providing stable readings
  • Proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it
  • Ergonomic design fits in your hand and can be used while wearing protective equipment
  • Large, easy to read backlight display automatically sets the correct measurement range so you do not need to change the switch positions while taking a measurement

Pro Sys CP41 Current Clamp Meter


The CP 41 current clamp meter has been designed for reliable and accurate, non-intrusive measurement of AC, DC and complex waveform currents. Using advanced Hall Effect technology the CP 41 can measure currents accurately from 5mA to 40Amps.

Measurement features include:

  • True RMS reading
  • 1mA/ 10mA Resolution
  • Auto ranging/Auto Power Off
  • Data Hold

Typical Applications

  • Leakage current measurements (CP41)
  • Process control for 4 – 20mA current loop verification (CP41)
  • Battery charging systems
  • Starting currents
  • Light industrial and residential electrical installation testing

10/08/2017

VT Testing

Omicron CP TD 1


Capacitance/dissipation factor testing device (tan delta)

Combined with the CPC 100, the CP TD1 measures the capacitance and dissipation factor (power factor) with laboratory precision.

This allows the insulation condition of transformers, generators and other parts of high-voltage systems to be tested according to IEEE 62 (C57.152), IEC 60076-1 and -3, as well as the CIGRE "Guide for Transformer Maintenance". As recommended in the CIGRE Guide, testing is performed at variable frequencies to better diagnose signs of ageing in insulation.

The portable test system (max. 29 kg per component) can also generate output voltages of up to 12 kV.

Key features

  • Testing at variable frequencies - better diagnosis of signs of ageing in insulation
  • Simple transport thanks to trolley - heaviest component just 29 kg
  • Excellent suppression of mains frequency interference fields
  • Automated testing – via PC using the Primary Test Manager software or via the user interface of the CPC 100 (includes testing templates)
  • Reporting - Detailed analysis with trend displays and graphics

Applications

The following variables can be measured by extending the CPC 100 to include the CP TD1:

  • Capacitance
  • Dissipation factor tan δ (tan delta)
  • Power factor cos φ
  • Watt losses
  • Power (effective power, apparent power, reactive power)
  • Impedance (absolute value, phase, inductance, resistance, quality)

Omicron CPC 100


Electrical tests on transformers, current transformers, voltage transformers, grounding systems, lines and cables, and circuit breakers can be performed with the CPC 100.

The patented test system replaces several individual testing devices and offers new, innovative testing methods.

The CPC 100 is the base for multiple accessories. These facilitate further applications, such as tan delta measurements, as well as line and ground impedance measurements.

Key features

  • Up to 800 A or 2000 V with up to 5 kVA over a frequency range of 15 Hz - 400 Hz or 400 A DC
  • Excellent interference suppression facilitates measurement of small signals
  • Easy to transport (just 29 kg) - Ideal for on-site testing
  • Testing templates, automatically generated testing procedures and test reports
  • Up to 2000 A or 12 kV through use of current or voltage amplifiers

Key features

Current transformers (CT)

  • Ratio, burden and polarity
  • Phase and magnitude error
  • Excitation curve
  • Winding resistance
  • Secondary burden
  • Dielectric withstand voltage (2 kV AC)
  • CT circuit continuity

Voltage transformers (VT)

  • Ratio, burden and polarity
  • Phase and magnitude error
  • Excitation curve
  • Winding resistance
  • Secondary burden
  • Dielectric withstand voltage (2 kV AC)
  • VT circuit continuity

Transformers

  • Ratio
  • Winding resistance
  • Tap changer test
  • Excitation current
  • Short circuit impedance
  • Transformer demagnetization

Lines and cables

  • Impedance (k-factor)
  • Transformer coupling

Grounding systems

  • Ground impedance
  • Step and touch voltages

Circuit breakers

  • Contact resistance

10/08/2017

TX Testing

Omicron CP TD 1


Capacitance/dissipation factor testing device (tan delta)

Combined with the CPC 100, the CP TD1 measures the capacitance and dissipation factor (power factor) with laboratory precision.

This allows the insulation condition of transformers, generators and other parts of high-voltage systems to be tested according to IEEE 62 (C57.152), IEC 60076-1 and -3, as well as the CIGRE "Guide for Transformer Maintenance". As recommended in the CIGRE Guide, testing is performed at variable frequencies to better diagnose signs of ageing in insulation.

The portable test system (max. 29 kg per component) can also generate output voltages of up to 12 kV.

Key features

  • Testing at variable frequencies - better diagnosis of signs of ageing in insulation
  • Simple transport thanks to trolley - heaviest component just 29 kg
  • Excellent suppression of mains frequency interference fields
  • Automated testing – via PC using the Primary Test Manager software or via the user interface of the CPC 100 (includes testing templates)
  • Reporting - Detailed analysis with trend displays and graphics

Applications

The following variables can be measured by extending the CPC 100 to include the CP TD1:

  • Capacitance
  • Dissipation factor tan δ (tan delta)
  • Power factor cos φ
  • Watt losses
  • Power (effective power, apparent power, reactive power)
  • Impedance (absolute value, phase, inductance, resistance, quality)

Omicron CPC 100


Electrical tests on transformers, current transformers, voltage transformers, grounding systems, lines and cables, and circuit breakers can be performed with the CPC 100.

The patented test system replaces several individual testing devices and offers new, innovative testing methods.

The CPC 100 is the base for multiple accessories. These facilitate further applications, such as tan delta measurements, as well as line and ground impedance measurements.

Key features

  • Up to 800 A or 2000 V with up to 5 kVA over a frequency range of 15 Hz - 400 Hz or 400 A DC
  • Excellent interference suppression facilitates measurement of small signals
  • Easy to transport (just 29 kg) - Ideal for on-site testing
  • Testing templates, automatically generated testing procedures and test reports
  • Up to 2000 A or 12 kV through use of current or voltage amplifiers

Key features

Current transformers (CT)

  • Ratio, burden and polarity
  • Phase and magnitude error
  • Excitation curve
  • Winding resistance
  • Secondary burden
  • Dielectric withstand voltage (2 kV AC)
  • CT circuit continuity

Voltage transformers (VT)

  • Ratio, burden and polarity
  • Phase and magnitude error
  • Excitation curve
  • Winding resistance
  • Secondary burden
  • Dielectric withstand voltage (2 kV AC)
  • VT circuit continuity

Transformers

  • Ratio
  • Winding resistance
  • Tap changer test
  • Excitation current
  • Short circuit impedance
  • Transformer demagnetization

Lines and cables

  • Impedance (k-factor)
  • Transformer coupling

Grounding systems

  • Ground impedance
  • Step and touch voltages

Circuit breakers

  • Contact resistance

Omicron FRAnalyzer


The FRAnalyzer (Frequency Response Analyzer) was developed for testing the integrity of power transformers after transportation or occurrence of high currents. The FRAnalyzer uses the SFRA principle (Sweep Frequency Response Analysis) and measures the electrical transfer function in a wide frequency range.

It detects winding defects and faults in the magnetic core - thereby helping to improve transformer reliability, reduce maintenance costs and prevent costly failures.

Key features

  • Reproducible results thanks to innovative connection technology
  • Extremely small and compact device (< 1.8 kg / 4 lbs)
  • Wide dynamic measuring range (> 120 dB)
  • Fast measurement times (around 30 seconds per measurement)

Applications

The FRAnalyzer is used for transformer testing, after:

  • A short circuit event
  • Transport
  • Occurrence of high transient fault currents
  • A significant change in the monitored values (e.g. combustible gases) or a safety shutdown

The following tests can also be performed:

  • Routine transformer condition measurement
  • Verification of unusual events determined during conventional testing

FLIR E6 Thermographic Camera


FLIR Ex-Series thermal imaging cameras are ideal for electrical and mechanical inspections where their ability to detect potential problem areas mean that installations can be quickly and easily inspected and breakdowns avoided. Building inspectors will also rapidly discover the benefits of the FLIR Ex-Series as they are ideal for detecting insulation losses, inspecting under floor heating and many other building related anomalies.

FLIR Ex-Series cameras are easy-to-use thermal imaging cameras that give the user access to a new dimension in inspection capability. An affordable replacement for a spot pyrometer, they provide a thermal image with temperature information on every pixel. A FLIR thermal imaging camera can scan an entire area, never missing a potential problem area, no matter how small it might be.

Outstanding ease-of-use

With a fixed focus-free lens, FLIR Ex-Series are extremely simple to operate.  Designed for entry-level users, and measuring temperatures up to +250°C, they produce instant, ‘point-and-shoot’ JPEG thermal imagery with all required temperature data included.

Visual camera and FLIR patented MSX

A built-in visual camera makes observing and inspecting faster and easier, as the visual image can be used as a reference against the thermal image. FLIR's patented MSX-technology provides thermal images of exceptional quality in real time. This results in sharper-looking thermal images, quicker target orientation and clutter-free reports.

  • Thermal image quality: 160x120 pixels
  • Thermal sensitivity: 0.06°C
  • IR image, visual image, MSX®, picture in picture, thumbnail gallery
  • Spotmeter, area with max./min., color alarm; blue below / red above set temperature

10/08/2017

Relay Testing

Omicron CMC 356


The CMC 356 is the universal solution for testing all generations and types of protection relays. Its powerful six current sources (three-phase mode: up to 64 A / 860 VA per channel) with a great dynamic range, make the unit capable of testing even high-burden electromechanical relays with very high power demands.

The CMC 356 is the first choice for applications requiring the highest versatility, amplitude and power. Commissioning engineers will particularly appreciate its ability to perform wiring and plausibility checks of current transformers, by using primary injection of high currents from the test set.

Key Features

  • Powerful current sources for testing even high-burden electromechanical relays
  • High current amplitudes for 5 A relay testing
  • High accuracy and versatility for testing static and numerical relays of all types
  • Integrated network for testing IEC 61850 IEDs
  • 10-channel analogue measurement and transient recording functionality (option)

Omicron CMGPS


When performing end-to-end tests of line protection schemes, it is necessary to start several test sets simultaneously. The CMGPS is a GPS-based synchronization unit which is used with CMC test equipment.

Applications

The CMGPS receives signals from the satellites of the Global Positioning System (GPS) and provides an output at a time specified by the user. This clock output is then used as a trigger input to start the CMC test set. The CMGPS has been developed to fulfil the requirements of testing in the field, because off-the-shelf GPS receivers with trigger output have many drawbacks (size, weight, complicated operation, etc.).

Further Information

CMGPS is typically ready for operation just 5 minutes after startup. The synchronizing pulse can be configured according to the requirements of the application. The software is integrated in the testing modules (like the State Sequencer). It allows for the setting of:

  • First output pulse
  • Pulse rate and polarity

Two independent timing pulses are available via separate connectors

  • Pulse out 1: 16-pin plug which is connected to the CMC test set (external interface)
  • Pulse out 2: two 4mm banana plugs

Omicron Current Clamp C-Probe 1


C-Probe 1 is an active AC and DC current probe with voltage output. It is the recommended accessory for measuring currents with the CMC 356 with ELT-1 hardware option or CMC 256plus and EnerLyzer software license.

Technical Data

  • Two measuring ranges: 10 A and 80 A
  • Frequency range: DC to 10 kHz
  • Accuracy: error < 2% for currents up to 40 A and frequencies up to 1 kHz

  • Phase error: < 0.5° at 50/60 Hz
  • Size: 230

10/08/2017

Power Supplies

DV Power Coil Analyzer SAT40A


Coil Analyzer SAT40A is a powerful instrument ideal for testing of circuit breakers, where substation battery is not connected or available. The SAT40A is intended to operate breaker coils, and spring charging motors as a part of commissioning and maintenance testing.

SAT30A measures current and resistance of circuit breaker coils. SAT40A can also be used to test minimum trip voltage of circuit breaker coils, as well as under voltage releases of circuit breaker. Output voltage is selectable from 10 V to 300 V DC or from 10 V to 250 V AC.

The set is equipped with thermal and over current protection. SAT40A is easy to use and has accessory cable-set with touch-proof contacts.

The SAT40A has very high ability to cancel electrostatic and electromagnetic interference in the HV electric fields. It is achieved by very efficient filtration. The filtration is made utilizing proprietary hardware and software.

DV POWER Coil Tester & Power Supply POB40AD


  • Circuit breaker coil operation
  • Spring-charging motor supply
  • Lightweight – only 10 kg
  • Minimum trip voltage test of the circuit breaker’s coils
  • As a power supply for tests with breaker analyzers from different vendors

Coil Tester & Power Supply POB40AD is powerful, lightweight power supply device, ideal for operating and testing circuit breakers coils. It is also intended to supply spring-charging motors with the possibility to generate the inrush current of up to 40 A. For supplying the circuit breaker auxiliary circuits, it provides wide output DC (10 – 300 V) and AC (10 – 250 V) voltage ranges.

POB40AD has built-in capability to perform an automatic test of minimum trip-voltage (in accordance to IEC 62271-100 and ANSI C37.09 standards).

POB40AD can be used as a general power supply device or a temporary battery charger. Note that it is compatible with the circuit breaker analyzers from different vendors.

Fluke 9040 Phase Rotation Meter


The Fluke 9040 is effective for measuring phase rotation in all areas where three phase supplies are used to feed motors, drives and electrical systems. The Fluke 9040 is a rotary field indicator and can provide clear indication of the 3 phase via an LCD display and the phase rotation direction to determine correct connections. It allows rapid determination of phase sequence and has a voltage (up to 700 V) and frequency range suitable for commercial and industrial applications. The included test probes have a variable clamping range for safe contact, also in industrial sockets.

Features

  • 3 phase indication
  • Indication of phase rotation
  • Clear LCD display
  • No battery required

10/08/2017

Line Testing

Omicron CPC 100


Electrical tests on transformers, current transformers, voltage transformers, grounding systems, lines and cables, and circuit breakers can be performed with the CPC 100.

The patented test system replaces several individual testing devices and offers new, innovative testing methods.

The CPC 100 is the base for multiple accessories. These facilitate further applications, such as tan delta measurements, as well as line and ground impedance measurements.

Key features

  • Up to 800 A or 2000 V with up to 5 kVA over a frequency range of 15 Hz - 400 Hz or 400 A DC
  • Excellent interference suppression facilitates measurement of small signals
  • Easy to transport (just 29 kg) - Ideal for on-site testing
  • Testing templates, automatically generated testing procedures and test reports
  • Up to 2000 A or 12 kV through use of current or voltage amplifiers

Key features

Current transformers (CT)

  • Ratio, burden and polarity
  • Phase and magnitude error
  • Excitation curve
  • Winding resistance
  • Secondary burden
  • Dielectric withstand voltage (2 kV AC)
  • CT circuit continuity

Voltage transformers (VT)

  • Ratio, burden and polarity
  • Phase and magnitude error
  • Excitation curve
  • Winding resistance
  • Secondary burden
  • Dielectric withstand voltage (2 kV AC)
  • VT circuit continuity

Transformers

  • Ratio
  • Winding resistance
  • Tap changer test
  • Excitation current
  • Short circuit impedance
  • Transformer demagnetization

Lines and cables

  • Impedance (k-factor)
  • Transformer coupling

Grounding systems

  • Ground impedance
  • Step and touch voltages

Circuit breakers

  • Contact resistance

10/08/2017

IR Testing

Fluke 1503 Insulation Resistance Tester


The Fluke 1507 and 1503 Insulation Testers are compact, rugged, reliable, and easy to use. With their multiple test voltages, they are ideal for many troubleshooting, commissioning, and preventative maintenance applications.

Additional features, like the remote probe on these tools save both time and money when performing tests.

Features:

  • Insulation test range:
    • 1507: 0.01 MΩ to 10 GΩ
    • 1503: 0.1 MΩ to 2000 MΩ
  • Insulation test voltages:
    • 1507: 50 V, 100 V, 250 V, 500 V, 1000 V
    • 1503: 500 V, 1000 V
  • Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio (only available on the1507)
  • Make repetitive tests simple and easy with the 1507’s Compare (Pass/Fail) function (only available on the 1507)
  • Repetitive or hard-to-reach testing is easy with the remote test probe
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • Auto-discharge of capacitive voltage for added user protection
  • AC/DC voltage: 0.1 V to 600 V
  • 200 mA Continuity
  • Resistance: 0.01 Ω to 20.00 kΩ
  • Save battery power with auto power off
  • Read measurements easily with large, backlit display
  • CAT IV 600 V overvoltage category rating for added user protection

Fluke 1507 1kV Insulation Resistance Tester


The Fluke 1507 and 1503 Insulation Testers are compact, rugged, reliable, and easy to use. With their multiple test voltages, they are ideal for many troubleshooting, commissioning, and preventative maintenance applications.

Additional features, like the remote probe on these tools save both time and money when performing tests.

Features:

  • Insulation test range:
    • 1507: 0.01 MΩ to 10 GΩ
    • 1503: 0.1 MΩ to 2000 MΩ
  • Insulation test voltages:
    • 1507: 50 V, 100 V, 250 V, 500 V, 1000 V
    • 1503: 500 V, 1000 V
  • Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio (only available on the1507)
  • Make repetitive tests simple and easy with the 1507’s Compare (Pass/Fail) function (only available on the 1507)
  • Repetitive or hard-to-reach testing is easy with the remote test probe
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • Auto-discharge of capacitive voltage for added user protection
  • AC/DC voltage: 0.1 V to 600 V
  • 200 mA Continuity
  • Resistance: 0.01 Ω to 20.00 kΩ
  • Save battery power with auto power off
  • Read measurements easily with large, backlit display
  • CAT IV 600 V overvoltage category rating for added user protection

Fluke 1555 Insulation Resistance Tester


The 1555 and redesigned Fluke 1550C insulation resistance testers, offer digital insulation testing up to 10kV, making them ideal for testing a wide range of high voltage equipment including switch gear, motors, generators and cables. Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating.

Features:

  • Test voltages up to 10 kV provides solutions for all applications
  • CAT III 1000 V, CAT IV 600 V safety rating
  • Voltage breakdown detection alerts the user that voltage is present and gives the voltage reading up to 600 V ac or dc for increased user safety
  • Selectable test voltages in 50 V steps from 250 to 1000 V, and 100 V steps above 1000 V
  • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
  • Long battery life gives the user over 750 tests between charges
  • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
  • Guard system eliminates the effect of surface leakage current on high-resistance measurements
  • Large digital/analogue LCD for easy viewing
  • Capacitance and leakage current measurement
  • Ramp function for breakdown testing
  • Resistance measurements up to 2TΩ
  • Timer settings up to 99 minutes for timed tests

Megger MIT1025


  • Measures up to 20 TΩ
  • PI, DAR, DD, SV and ramp test
  • Improved productivity – operate from line power/mains if battery dead
  • Li ion battery - extended capacity, rapid charge
  • Advanced memory with time/date stamp
  • CATIV 600 V safety rating

Offering CAT IV, the MIT1025 is compact, light 10 kV insulation resistance tester for the diagnostic testing and maintenance of high voltage electrical equipment. Enclosed in a tough case it is both smaller and lighter than its predecessor making it even easier to carry and store.

As well as measuring insulation resistance to 20 TΩ, the MIT1025 also offers various diagnostic tests such as Polarisation index, Dielectric Absorption Ratio, Step Voltage, Dielectric discharge and ramp testing.

Now equipped with lithium ion fast rechargeable batteries, the instrument has a large, clear, easy to read, display making it equally suitable for use in both bright sunlight and poorly lit environments. Information displayed includes resistance, voltage, leakage current, capacitance, battery status and time constant. In addition, the elapsed time of the test is displayed constantly removing the need for separate timer.

Page 5 of 37

Don’t see what you need? Send a general enquiry using the button below and we’ll take care of it.